Pacific Radio (M) Sdn Bhd
[16370-U]
80, Jalan Pasar, Pudu,
55100 Kuala Lumpur,
Malaysia.
 +603-9221 8631 (6 Lines)

 +603-9221 4216
 +603-9221 3867
 +6018-208 2618
 +603-9221 8630

 +603-9223 4109

 
Pacific Electronic (S) Pte Ltd
1 Rochor Canal Road,
#01-10/11/12,
Sim Lim Square,
Singapore 188504.
 +65-6294 0851
 +65-6337 1132
 +65-6339 5884
 +65-6339 8454
 +65-6338 3609

Kyoritsu 6010B Multi Function Testers

Previous 3 / 4 Next

Kyoritsu 6010B Multi Function Testers KYORITSU Multi Function Testers Kyoritsu 6010B Multi Function Testers KYORITSU Multi Function Testers


Download Files

Catalogue_Kyoritsu_6010B.pdf (1.02 MB)
• Continuity:20/200Ω 200mA Test Current
• Insulation: 500/1000V, 20/200MΩ 1mA Rated Test Current
• Loop Impedance:20/2000Ω 15mA Test Current at 2000Ω (No RCD Trip)
• RCD:10/30/100/300/500mA x1/2, x1, Fast Trip(40ms), DC, Auto Ramp
• Test of a large kind of RCD's:Standard, Selective, AC and A(DC sensitive breakers)
• Uc(Contact Voltage): 100V
• Designed to IEC 61010-1, IEC 61557
• Data Memory:300 measured results
• The stored data can be transferred to PC via Optical Adaptor Model 8212-USB or 8212-RS232C.
 
Continuity Testing
Measuring Range 20/200Ω (Auto-Ranging)
Open Circuit Voltage > 6V
Short Circuit Current > 200mA
Accuracy ±(3%rdg + 3dgt)
Insulation Resistance Testing
Measuring Range 20/200MΩ (Auto-Ranging)
Test Voltage 500/1000V
Open Circuit Voltage +20% - 0%
Rated Current > 1mA
Accuracy ± (3%rdg + 3dgt)
Loop Impedance Testing
Impedance Range 20/2000Ω
Rated Voltage 230V + 10% - 15%(50Hz)
Normal Test Current 20Ω:25A/10ms
2000Ω:15mA/350ms max.
Accuracy ±(3%rdg + 8dgt)
RCD Testing
Test Current
(Test Current Duration)
x1/2, x1 10, 30, 100, 300, 500mA (2000ms)
Fast 150mA (50ms)
DC 10, 30, 100, 300mA (2000ms), 500mA (200ms)
Auto Ramp Goes up by 10% from 20% to 110% of IΔn. 300ms×10
Rated Voltage 230V + 10% - 15% 50Hz
Accuracy Test Current x1/2: -8%-2%
x1, FAST: +2%+8%
DC: ±10%
Auto Ramp: ±4%
Trip Time ±(1%rdg + 3dgt)
Uc Testing
Measuring Range 100V
Rated Voltage 230V + 10% - 15% (50Hz)
Test Current 5mA at IΔn = 10mA
15mA at IΔn = 30/100mA
150mA at IΔn = 300/500mA
Accuracy +5%+15%rdg, ±8dgt
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61557-1, 2, 3, 4, 6, 10, IEC 60529 (IP40)
Power source R6 or LR6 × 8
Dimensions 175(L) × 115(W) × 86(D)mm
Weight 840g approx.
Included Accessories 7122B (Test leads) 
KAMP10* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
Instruction Manual
Optional Accessories 7133B (Distribution board test leads)
8212-RS232C (RS232C adaptor with "KEW Report (Software)")
8212-USB (USB adaptor with "KEW Report (Software)")

*KAMP10 (AU): Australian plug
  KAMP10 (UK): British plug (13A)
  KAMP10 (EU): European SHUKO plug
  KAMP10 (SA): South African plug


Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Ship to Name  
Shipping Address  
Attachment  
*only support gif, jpeg, jpg, png, pdf
Messages*  

Switch to Mobile Version