Fluke Insulation Testers - Fluke 1587 and 1577 Insulation Multimeters

Previous 2 / 2 Next

Fluke Insulation Testers - Fluke 1587 and 1577 Insulation Multimeters FLUKE Digital Insulation Tester


Specifications
Voltage DC
Maximum Voltage:  1000 V
Accuracy:  1577: ±(0.2%+2)
   1587: ±(0.09%+2)
Maximum Resolution:  0.001V
Voltage AC
Maximum Voltage:  1000 V
Accuracy:  1577: ±(2%+3)
   1587: ±(2%+3)
AC Bandwidth:  1587: 5kHz*
   *with low pass filter; 3db @ 800 Hz
Maximum Resolution:  0.1 mV
Current DC
Maximum Amps:  400mA
Amps Accuracy:  1577: ±(1.0%+2)
   1587: ±(0.2%+2)
Maximum Resolution:  0.01 mA
Current AC
Maximum Amps:  400mA
Amps Accuracy:  1577: ±(2.0%+2)*
   1587: ±(1.5%+2)*
   * 1kHz bandwidth
Maximum Resolution:  0.01 mA
Resistance
Maximum Resistance:  50 MΩ
Accuracy:  1577: ±(1.2%+2)
   1587: ±(0.9%+2)
Maximum Resolution:  0.1Ω
Capacitance(1587 only)
Maximum Capacitance:  9,999 µF
Accuracy:  ±(1.2%+2)
Maximum Resolution:  1 nF
Frequency (1587 only)
Maximum Frequency:  100 kHz
Accuracy:  ±(0.1%+1)
Maximum Resolution:  0.01 Hz
Temperature Measurement (1587 only)
   -40.0 °C to 537 °C
   -40.0 °F to 998 °F
   excluding probe
Diode Test (1587 only)
Range:  6 V
Resolution:  1 mV
Accuracy:  ±(2 % + 1)

Insulation Test
Minimum Test Current @ 1kΩ/V:
   1mA
Test Voltages:
1577:  500, 1000 V
1587:  50, 100, 250, 500, 1000 V
Maximum Resistance per Test Voltage:
50V:  
100V:  
250V:  
500V:  
1000V:  1577: 600 MΩ
   1587: 2 GΩ
Maximum Resolution per Test Voltage:
50V:  0.01 MΩ
100V:  0.01 MΩ
250V:  0.1 MΩ
500V:  0.1 MΩ
1000V:  0.1 MΩ
Accuracy per Test Voltage:
50V:  ±(3 % + 5)
100V:  ±(3 % + 5)
250V:  ±(1.5 % + 5)
500V:  1577: ±(2.0 % + 5)
   1587: ±(1.5 % + 5)
1000V:  1577: ±(2.0 % + 5)
   1587: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ

Environmental Specifications
Operating temperature
   –20 °C to +55 °C
Storage temperature
   -40°C to +60°C
Humidity (Without Condensation)
   0% - 95% (10 °C – 30 °C)
   0% - 75% (30 °C – 40 °C)
   0% - 40% (40 °C – 55 °C)
Operating Altitude
   2000 m

Safety Specifications
Overvoltage category
   Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
Agency Approvals
   2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V

Mechanical & General Specifications
Size
   203 x 100 x 50 mm (with holster)
Weight
   624 g
Warranty
   3 years
Battery life Alkaline
Meter use:  1000 hours
Insulation test use:  Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
IP Rating
   IP40
Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Ship to Name  
Shipping Address  
Attachment  
*only support gif, jpeg, jpg, png, pdf